Second Notice ELE | 10/10/2006 | 10/10/2006 | 10/18/2006 | | DONE |
|
|
|
This permit finaled on the web by Cindie Swaim
|
First Notice | 9/29/2006 | 9/29/2006 | 10/10/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 9/28/2006 | 9/29/2006 | 9/29/2006 | A | PASS |
Bob Reichert
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ok to final, signed card
|
Final | 9/28/2006 | 9/28/2006 | 9/28/2006 | P | FAIL |
Bob Reichert
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, nec 210.62 at least 1 recpt shall be installed directly above a show window, 358.30(A) emt shall be securely fastened within 3' of box, 725.3(B) abandoned cable (TV) shall be removed(cl2,3,or pltc) 300.11(A) support wires that do not provide secure support shall not be permitted
|
Rough-In Permanent Service | 9/8/2006 | 9/11/2006 | 9/11/2006 | A | PASS |
Bob Reichert
|
|
|
allan; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley walls only ok to cover, called contr to add 1 strap and advised showroom recpts will be required
|
Application received | | | 9/6/2006 | | DONE |
|
|
|
This permit was created on the web by Cindie Swaim
|