Final | 12/5/2006 | 12/6/2006 | 12/6/2006 | A | PASS |
Jack Frank
|
|
|
Please call ###-#### with problems or questions. Thank You. Internet Inspection Request from: Latisha Peltier ok
|
Rough-In Permanent Service | 9/8/2006 | 9/8/2006 | 9/8/2006 | A | PASS |
Bob Reichert
|
|
|
reinspection Internet Inspection Request from: Latisha Peltier corr made, ric ok, p/s u/g rec ok
|
Rough-In Permanent Service | 9/7/2006 | 9/7/2006 | 9/7/2006 | P | FAIL |
Bob Reichert
|
|
|
Internet Inspection Request from: Latisha Peltier called contr, left message, left corr notice, nec 408.4 circuit directory shall be done, 250.68(A) gec connection shall be accessible, 210.52(A)(2) by up bath wall shall have recpt in 2' wall space in big room,300.4(A) edge of bored hole shall be 1 1/4" from edge of framing member, BCC all make-up shall be done-hall and sink lites
|
Application received | | | 9/7/2006 | | DONE |
|
|
|
This permit was created on the web by Latisha Peltier
|