Final | 11/20/2006 | 11/20/2006 | 11/20/2006 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/20/2006 at 7:34:39 AM. Contact: ###-####. ok to final
|
Rough-In Permanent Service | 9/13/2006 | 9/13/2006 | 9/13/2006 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/13/2006 at 5:23:39 AM. Contact: ###-####. r/i p/s u/g new ok
|
Electrical Rough-In | 9/12/2006 | 9/12/2006 | 9/12/2006 | P | NR |
Jack Frank
|
|
|
brannon; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley talked with contr corr. not made
|
Rough-In Permanent Service | 9/12/2006 | 9/12/2006 | 9/12/2006 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/12/2006 at 6:47:58 AM. Contact: ###-####. corr. called still needs nail plates and protect all cables by attic accesses
|
Reinspection Fee (no hold) | 9/12/2006 | 9/12/2006 | 9/12/2006 | A | DONE |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/12/2006 at 6:47:58 AM. Contact: ###-####. fee due all corrections not made
|
Rough-In Permanent Service | 9/8/2006 | 9/11/2006 | 9/11/2006 | A | FAIL |
Jack Frank
|
|
|
Internet Inspection Request from: Rowdy Monroe corr. called 300.4 nail plates, 210.52(A&B) needs outlet wall space kit by pantry, 334.23 protect cables by attic accesses, 250.70 install grd wire in terminal at grd clamp not between clamp and rebar, update permit for 17 rms
|
Electrical Rough-In | 9/8/2006 | 9/11/2006 | 9/11/2006 | A | CANC |
Jack Frank
|
|
|
Internet Inspection Request from: Rowdy Monroe
|
Application received | | | 9/8/2006 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|