Final | 4/5/2007 | 4/5/2007 | 4/5/2007 | P | PASS |
Pat Lass
|
|
|
the key is under the lip of the first column on the right hand side of the front stairs. Between the rocks and the wood. Phone #: ###-####
|
Final | 2/5/2007 | 2/5/2007 | 2/5/2007 | P | NR |
Pat Lass
|
|
|
jack - call for key location; Phone #: ###-#### Internet Inspection Request from: Victoria Beall tripped breaker and outlets not working
|
Electrical Rough-In | 9/20/2006 | 9/20/2006 | 9/20/2006 | P | PASS |
Jack Frank
|
|
|
jack - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
|
Permanent Service | 9/18/2006 | 9/18/2006 | 9/18/2006 | P | PASS |
Jack Frank
|
|
|
p/s o/h new ok
|
Rough-In Permanent Service | 9/18/2006 | 9/18/2006 | 9/18/2006 | P | FAIL |
Jack Frank
|
|
|
jack ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called 300.4 (A)(1) still needs nail plates for holes where holes are less than 11/4" from edges of framing members as code noted states see added p/s
|
Electrical Rough-In | 9/12/2006 | 9/12/2006 | 9/12/2006 | P | FAIL |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tollie Rogers nec330.4(D) 1 1/4 inch support from edge of framing members. (throughout the house) note service romex connectors have to be approved for 2 or more cables. ground rod shall be drivin at 45 degree angle or more.
|
Application received | | | 9/12/2006 | | DONE |
|
|
|
This permit was created on the web by Tollie Rogers
|