Final | 9/14/2006 | 9/15/2006 | 9/15/2006 | A | PASS |
Jack Frank
|
|
|
seth; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
|
Permanent Service | 9/15/2006 | 9/15/2006 | 9/15/2006 | A | PASS |
Jack Frank
|
|
|
seth; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley p/s o/h rec. ok
|
Permanent Service | 9/14/2006 | 9/14/2006 | 9/14/2006 | P | FAIL |
Jack Frank
|
|
|
Seth; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. 250.52(A)(1) or 104(A)(1) grd or bond water system at service not subpanel, 250.53 grd rods shall be 6ft apart, 110.12(A) seal all KOs, conn. for GEC, install backfeed clip
|
Reinspection Fee (no hold) | 9/14/2006 | 9/14/2006 | 9/14/2006 | P | DONE |
Jack Frank
|
|
|
Seth; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. and fee due met contr.
|
Permanent Service | 9/13/2006 | 9/13/2006 | 9/13/2006 | P | FAIL |
Jack Frank
|
|
|
seth; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called left message need to talk to contr. shall bring p/s up to current code grd. bond, clearence needs service disconnect , address subpanel
|
Application received | | | 9/12/2006 | | |
|
|
|
|
Issue permit | | | 9/12/2006 | | DONE |
|
|
|
|