Second Notice ELE | 12/26/2006 | 12/26/2006 | 12/29/2006 | | DONE |
|
|
|
This permit finaled on the web by Sean DeLacy
|
First Notice | 11/2/2006 | 11/2/2006 | 12/26/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 11/1/2006 | 11/2/2006 | 11/2/2006 | P | PASS |
Bob Reichert
|
|
|
PAUL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy corr made, ok to final
|
Final | 10/26/2006 | 10/26/2006 | 10/26/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy met contr,left corr notice, nec 314.15(A) in wet locations, fittings shall be listed for use in wet locations, 110.26(A) work space about panel shall be 3' clear distance in front of panel, BCC kitchen area outlets shall operate, no violations shall be retained
|
Electrical Rough-In | 10/17/2006 | 10/18/2006 | 10/18/2006 | A | PASS |
Jack Frank
|
|
|
PAUL CEILING COVER INSPECTION; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
|
Electrical Rough-In | 9/28/2006 | 9/28/2006 | 9/28/2006 | P | PART |
Jack Frank
|
|
|
PAUL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy walls , hard ceilings up&downstairs
|
Electrical Rough-In | 9/14/2006 | 9/14/2006 | 9/14/2006 | P | PART |
Jack Frank
|
|
|
PAUL UNDERGROUND INSPECTION; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok
|
Application received | | | 9/13/2006 | | DONE |
|
|
|
This permit was created on the web by Sean DeLacy
|