Permit NumberELE06-03454
StatusFinaled
Name CORNERSTONE ELECTRIC
Site Address 2275 E SKIPPERLING LN
Project Name 
Customer Number 
ePlanReview 
Description
added circuits
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/4/200612/4/200612/4/2006PPASS
DetailsMike Kinnear
cal - call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok final
Electrical Rough-In9/18/20069/18/20069/18/2006PPASS
DetailsMike Kinnear
cal; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok cover ri corrections made
Electrical Rough-In9/15/20069/15/20069/15/2006PFAIL
DetailsBob Reichert
cal - call prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left corr notice, nec 210.52(A)(1) recpts shall be installed in mud room and top of stairs for 6'-12' spacing, 210.52(E) at least 1 recpt shall be at back of dwelling, 210.52(D) recpt shall be installed within 3' of each basin in bath, 210.11(C)(3) bath circuits shall be dedicated 20a branch circuits, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, or covered with steel plates, 250.86 metal enclosure in hall for light shall be grounded, 210.12(B) bedrooms shall be afci protected, BCC all make-up shall be done, smoke detectors shall be installed in required areas, no violations shall be retained Note, later told contr that if no work done in room recpt would not have to be installed (bath)
Application received  9/15/2006  
Issue permit  9/15/2006 DONE