Electrical Rough-In | 9/18/2006 | 9/19/2006 | 9/19/2006 | A | FAIL |
Jack Frank
|
|
|
Work performed by Jim Duffy.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz corr. called left message, 680.22(A)(3) outlet 10 ft 20 ft from spa, 250.24(A)(5) remove equip grd from neutral bus at subpanel, 220.40 service too small with spa added only 100 A
|
Application received | | | 9/18/2006 | | DONE |
|
|
|
This permit was created on the web by Matt Santacruz
|