Permanent Service | 6/12/2007 | 6/13/2007 | 6/13/2007 | A | PASS |
William E Thomas
|
|
|
erik ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 1. p/s o/h reconnect/new ok 2. this is for p/s only, no interior inspection for ri has been done.
|
ELE-Request for Extension | 3/19/2007 | 3/20/2007 | 3/20/2007 | A | CANC |
Jim Schmer
|
|
|
Eric Lund ###-#### one time onlyu
|
Electrical Rough-In | 3/16/2007 | 3/19/2007 | 3/19/2007 | A | NR |
Bob Reichert
|
|
|
Erick Panel and Meter; Phone #: ###-#### Internet Inspection Request from: Stacie Backus met owner, told needed 2 ground rods, water pipe ground, abrasion protection, checked o/h and clearance is ok, use plastic not metal between meter and panel, said meter location ok
|
Application received | | | 9/20/2006 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/20/2006 | | DONE |
|
|
|
|