Third Notice ELE | 2/9/2007 | 2/9/2007 | 4/10/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Telephone call | | | 4/6/2007 | | DONE |
|
|
|
t/c w lloyd at ###-#### - said he will fax in the final value today
|
Second Notice ELE | 12/26/2006 | 12/26/2006 | 2/9/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 10/16/2006 | 10/16/2006 | 12/26/2006 | | DONE |
Jack Frank
|
|
|
|
Final | 10/16/2006 | 10/16/2006 | 10/16/2006 | P | PASS |
Jack Frank
|
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok card signed
|
Final | 10/13/2006 | 10/13/2006 | 10/13/2006 | P | FAIL |
Bob Reichert
|
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, corrctions not complete, shall not use ceiling grid wires for raceway support, bkr openings shall be closed, strap mc cable out of box, ckt directory shall be explicit, 370 put ok by corrected items on corr notice
|
Reinspection Fee (no hold) | 10/13/2006 | 10/13/2006 | 10/13/2006 | A | NH |
Bob Reichert
|
|
|
called with no access, contr not ready, left card
|
Final | 10/12/2006 | 10/13/2006 | 10/13/2006 | A | NH |
Bob Reichert
|
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called said to call when can get in
|
Final | 10/12/2006 | 10/12/2006 | 10/12/2006 | P | FAIL |
Bob Reichert
|
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, nec 210.62 showroom receptacles shall be installed every 12' or fraction thereof for show windows, 408.4 circuit directory shall be clear, concise, and provide sufficient detail to distinguish each circuit, 110.12(A) unused openings shall be closed, 300.11(A) shall use support wires for fixtures, cables shall be supported, 725.3(B) abandoned cables shall be removed,BCC no cover shall be done prior to inspection(ceiling)
|
Electrical Rough-In | 9/22/2006 | 9/22/2006 | 9/22/2006 | P | PASS |
Bob Reichert
|
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr about nail plates, walls only ok to cover
|
Electrical Rough-In | 9/21/2006 | 9/22/2006 | 9/22/2006 | A | NH |
Bob Reichert
|
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left card
|
Application received | | | 9/20/2006 | | |
|
|
|
|
Issue permit | | | 9/20/2006 | | DONE |
|
|
|
|