Permit Information
Permit NumberELE06-03531
StatusFinaled
Name LLOYDS ELECTRIC
Site Address 12505 W CHINDEN BLVD Unit: 103
Project NameBOISE RESEARCH CNTR #3
Customer Number 
ePlanReview 
Description
remodel - add conv. plugs and modify switching per initial cert of value $4600.00 ///final value remains the same per faxed document 4-10-07ps
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice ELE2/9/20072/9/20074/10/2007 DONE
Second Notice has not been responded to.
Telephone call  4/6/2007 DONE
t/c w lloyd at ###-#### - said he will fax in the final value today
Second Notice ELE12/26/200612/26/20062/9/2007 DONE
First Notice has not been responded to.
First Notice10/16/200610/16/200612/26/2006 DONE
DetailsJack Frank
Final10/16/200610/16/200610/16/2006PPASS
DetailsJack Frank
lloyd; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok card signed
Final10/13/200610/13/200610/13/2006PFAIL
DetailsBob Reichert
lloyd; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, corrctions not complete, shall not use ceiling grid wires for raceway support, bkr openings shall be closed, strap mc cable out of box, ckt directory shall be explicit, 370 put ok by corrected items on corr notice
Reinspection Fee (no hold)10/13/200610/13/200610/13/2006ANH
DetailsBob Reichert
called with no access, contr not ready, left card
Final10/12/200610/13/200610/13/2006ANH
DetailsBob Reichert
lloyd; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called said to call when can get in
Final10/12/200610/12/200610/12/2006PFAIL
DetailsBob Reichert
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, nec 210.62 showroom receptacles shall be installed every 12' or fraction thereof for show windows, 408.4 circuit directory shall be clear, concise, and provide sufficient detail to distinguish each circuit, 110.12(A) unused openings shall be closed, 300.11(A) shall use support wires for fixtures, cables shall be supported, 725.3(B) abandoned cables shall be removed,BCC no cover shall be done prior to inspection(ceiling)
Electrical Rough-In9/22/20069/22/20069/22/2006PPASS
DetailsBob Reichert
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr about nail plates, walls only ok to cover
Electrical Rough-In9/21/20069/22/20069/22/2006ANH
DetailsBob Reichert
lloyd; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left card
Application received  9/20/2006  
Issue permit  9/20/2006 DONE