Second Notice ELE | 10/10/2006 | 10/10/2006 | 10/11/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 9/29/2006 | 9/29/2006 | 10/10/2006 | | DONE |
Jack Frank
|
|
|
|
Temporary Service | 9/29/2006 | 9/29/2006 | 9/29/2006 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: TJ Sturges t/s o/h new ok
|
Temporary Service | 9/27/2006 | 9/28/2006 | 9/28/2006 | A | FAIL |
Jack Frank
|
|
|
overhead temporary power; Phone #: ###-#### Internet Inspection Request from: TJ Sturges corr. fee due not ready patrial corr 250.32(A)&(B)(1) needs grd rod at job trailer, 310.16 and 110 .3 (B) manu. building states 100 amp shall provide 100 wire
|
Reinspection Fee (no hold) | 9/28/2006 | 9/28/2006 | 9/28/2006 | A | DONE |
Jack Frank
|
|
|
overhead temporary power; Phone #: ###-#### Internet Inspection Request from: TJ Sturges fee due job not ready and corr.
|
Application received | | | 9/27/2006 | | DONE |
|
|
|
This permit was created on the web by TJ Sturges
|