Final | 10/12/2006 | 10/12/2006 | 10/12/2006 | P | PASS |
Bob Reichert
|
|
|
lee; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, see p/s
|
Permanent Service | 10/12/2006 | 10/12/2006 | 10/12/2006 | P | PASS |
Bob Reichert
|
|
|
lee; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s rec n ok
|
Permanent Service | 10/6/2006 | 10/6/2006 | 10/6/2006 | P | FAIL |
Bob Reichert
|
|
|
brynt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left 2 messages, left corr notice, nec 550.11(A) a single disconnect shall be provided at an accessible location and plainly marked main,334.15(B) nm cable shall be protected from physical damage (below panel),310.15(B)(6) 200a breaker shall not protect 150a rated panel
|
Final | 10/5/2006 | 10/5/2006 | 10/5/2006 | P | CANC |
Bob Reichert
|
|
|
Brent; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr, no address, no job id sticker
|
Application received | | | 10/5/2006 | | |
|
|
|
|
Issue permit | | | 10/5/2006 | | DONE |
|
|
|
|