Final | 4/18/2007 | 4/18/2007 | 4/18/2007 | P | PASS |
Bob Reichert
|
|
|
RON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
|
Final | 4/17/2007 | 4/18/2007 | 4/18/2007 | A | FAIL |
Bob Reichert
|
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, nec 406.4 recpts shall be securely mounted, 406.4(D) recpts shall be flush with or project from faceplates, 110.3(B) listed equip shall be installed according to instructions-faceplate screws, 110.22 each disconnect shall be legibly marked to indicate it's purpose
|
Electrical Rough-In | 3/16/2007 | 3/16/2007 | 3/16/2007 | P | PASS |
Bob Reichert
|
|
|
ron Trench; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok to cover u/g house to garage
|
Rough-In Permanent Service | 10/6/2006 | 10/9/2006 | 10/9/2006 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/6/2006 at 3:42:50 PM. Contact: ###-####. r/i p/s u/g new ok
|
Rough-In Permanent Service | 10/6/2006 | 10/6/2006 | 10/6/2006 | P | NR |
Jack Frank
|
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Patricia Smith needs addresses
|
Application received | | | 10/6/2006 | | |
|
|
|
|
Issue permit | | | 10/6/2006 | | DONE |
|
|
|
|