Final | 4/18/2007 | 4/18/2007 | 4/18/2007 | P | PASS |
Bob Reichert
|
|
|
RON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
|
Final | 4/17/2007 | 4/18/2007 | 4/18/2007 | A | FAIL |
Bob Reichert
|
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, nec 110.22 each disconnect shall be legibly marked to indicate it's purpose, 210.8(A) garage gfci shall operate-downstream, 406.4 receptacles shall be securely mounted, 408.4 circuit directory shall be clear, complete, concise and explanatory
|
Electrical Rough-In | 3/16/2007 | 3/16/2007 | 3/16/2007 | P | PASS |
Bob Reichert
|
|
|
ron Trench; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok to cover trench house to garage
|
Rough-In Permanent Service | 10/6/2006 | 10/9/2006 | 10/9/2006 | A | PASS |
Jack Frank
|
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Patricia Smith r/i p/s new ok
|
Application received | | | 10/6/2006 | | |
|
|
|
|
Issue permit | | | 10/6/2006 | | DONE |
|
|
|
|