Second Notice ELE | 12/26/2006 | 12/26/2006 | 2/2/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 10/23/2006 | 10/23/2006 | 12/26/2006 | | DONE |
Mike Kinnear
|
|
|
|
Final | 10/20/2006 | 10/23/2006 | 10/23/2006 | A | PASS |
Mike Kinnear
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok final corrections made signed card
|
Final | 10/20/2006 | 10/20/2006 | 10/20/2006 | P | FAIL |
Bob Reichert
|
|
|
randy; Phone #: ###-#### - note: call 1/2 prior to going out - Internet Inspection Request from: Patricia Smith corrections not all made, also, now that final, mech room needs lite and recpt, fixt connector shall be tight, box too full, open ko's in box, fee due
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 10/20/2006 | | |
|
|
|
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 10/20/2006 | | |
|
|
|
|
Electrical Rough-In | 10/18/2006 | 10/18/2006 | 10/18/2006 | P | FAIL |
Bob Reichert
|
|
|
randy - note: ceiling ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice, nec 330.30(B) mc shall be strapped within 12" of box, 348.30(A) fmc shall be strapped within 12" of box, 110.12(A) unused openings in boxes shall be closed, 300.31 box covers shall be installed, BCC fixtures shall be secured in place with minimum 2 support wires, BCC no violation shall be retained
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 10/18/2006 | | |
|
|
|
|
Electrical Rough-In | 10/12/2006 | 10/13/2006 | 10/13/2006 | P | PART |
Jack Frank
|
|
|
loren; Phone #: - note: suite 103 - ###-#### Internet Inspection Request from: Patricia Smith walls ok
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 10/12/2006 | | |
|
|
|
|
Application received | | | 10/9/2006 | | DONE |
|
|
|
This permit was created on the web by Steve Syltie
|