Final | 12/6/2006 | 12/8/2006 | 12/8/2006 | P | PASS |
Pat Lass
|
|
|
ted; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Electrical Rough-In | 10/24/2006 | 10/24/2006 | 10/24/2006 | P | PASS |
Pat Lass
|
|
|
ted; Phone #: ###-#### Internet Inspection Request from: Patricia Smith electrode ok
|
Permanent Service | 10/24/2006 | 10/24/2006 | 10/24/2006 | P | PASS |
Pat Lass
|
|
|
ted; Phone #: ###-#### Internet Inspection Request from: Patricia Smith P/S O/H R Ok
|
Electrical Rough-In | 10/19/2006 | 10/19/2006 | 10/19/2006 | P | PASS |
Pat Lass
|
|
|
ted - note: re-inspection - please call after inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith wall in back of service ok
|
Final | 10/18/2006 | 10/18/2006 | 10/18/2006 | P | CANC |
Mike Kinnear
|
|
|
ted; Phone #: ###-#### Internet Inspection Request from: Patricia Smith wrong type inspection
|
Electrical Rough-In | 10/18/2006 | 10/18/2006 | 10/18/2006 | P | PART |
Mike Kinnear
|
|
|
ted; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok cover ground wire with concrete
|
Rough-In Permanent Service | 10/10/2006 | 10/11/2006 | 10/11/2006 | A | FAIL |
Pat Lass
|
|
|
ted; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 338.24 bending radius for cable 250.50 connect old water service to electrode system install concrete encased electrode 250.24 connect electrode system to system grounded conductor 250.28 install main bonding jumper 2 in. is required for mast as support.
|
Electrical Rough-In | 10/11/2006 | 10/11/2006 | 10/11/2006 | P | PASS |
Pat Lass
|
|
|
ted; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
Application received | | | 10/10/2006 | | |
|
|
|
|
Issue permit | | | 10/10/2006 | | DONE |
|
|
|
|