Final | 12/18/2006 | 12/19/2006 | 12/19/2006 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 12/18/2006 at 1:45:36 PM. Contact: ###-####.
|
Electrical Rough-In | 10/11/2006 | 10/11/2006 | 10/11/2006 | P | PASS |
Pat Lass
|
|
|
brandon -re-insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
Electrical Rough-In | 10/10/2006 | 10/10/2006 | 10/10/2006 | P | FAIL |
Jack Frank
|
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Darla Downs corr. met owner corr. note owner did not not call for conference before r/i 110.14(B) shall complete all makeup and use approved devices for splices wires just twisted, 210.52(A) needs outlets for 2ft walls entry to bedrm ,wall by door to closet, 300.4(A)(!)&(D) nail plates adn 11/4" parallel, 210.11(C)(3)&210.52(D) remove hall outlet from bath circuit, 300.14 needs 6" free length all location, explained everything to owner , owner just wanted to argue
|
Application received | | | 10/10/2006 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/10/2006 | | DONE |
|
|
|
|