Second Notice ELE | 2/9/2007 | 2/9/2007 | 2/16/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 1/26/2007 | 1/26/2007 | 2/9/2007 | | DONE |
Bob Reichert
|
|
|
|
Final | 1/25/2007 | 1/26/2007 | 1/26/2007 | A | PASS |
Bob Reichert
|
|
|
eddie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr to install water heater disconnects, ok to final
|
Electrical Rough-In | 10/13/2006 | 10/16/2006 | 10/16/2006 | A | CANC |
Bob Reichert
|
|
|
eddie; Phone #: ###-#### Internet Inspection Request from: Patricia Smith wrong type inspection, see rip
|
Rough-In Permanent Service | 10/16/2006 | 10/16/2006 | 10/16/2006 | A | PASS |
Bob Reichert
|
|
|
eddie; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 10/12/2006 | 10/12/2006 | 10/12/2006 | P | FAIL |
Jack Frank
|
|
|
eddie; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr. called 300.4(A)(1) nail plates everywhere, 210.52(A&B) required outlets liv. rm din. rm din. shall not serve liv. , the same liv rm, 210.52(C) outlets for countertops
|
Reinspection Fee (no hold) | 10/12/2006 | 10/12/2006 | 10/12/2006 | P | DONE |
Jack Frank
|
|
|
eddie; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr. fee due
|
Rough-In Permanent Service | 10/11/2006 | 10/12/2006 | 10/12/2006 | A | FAIL |
Jack Frank
|
|
|
eddie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called needs access to 2nd floor no stairs or ladder called
|
Application received | | | 10/11/2006 | | |
|
|
|
|
Issue permit | | | 10/11/2006 | | DONE |
|
|
|
|