Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE06-03798
StatusFinaled
Name ALL AMERICAN ELECTRIC
Site Address 2118 N CRIBBENS ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/11/20074/12/20074/12/2007APASS
DetailsJack Frank
Phone #: ###-#### ok
Rough-In Permanent Service10/18/200610/18/200610/18/2006PPASS
DetailsJack Frank
reinspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman r/i for new part ok, note Jtub not there check for listing when installed
p/s o/h rec. ok
Rough-In Permanent Service10/17/200610/17/200610/17/2006PFAIL
DetailsJack Frank
reinspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman corr. fee due called, 300.4(A)(1)&(D) nail plates and 11/4" for cables parallel, 334.30 staple cables 12" or 8" as code states, 314.43 no screws in plastic boxes, note grd or bond new p/s to water system old part of house, 250.52(A)(1) or 104(A)(1)
Reinspection Fee (no hold)10/17/200610/17/200610/17/2006PDONE
DetailsJack Frank
reinspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman not all corr. made corr fee due
Electrical Rough-In10/13/200610/13/200610/13/2006PFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: DJ Carman called, left corr notice, nec 404.8 center operating handle shall not be over 6'-7", 312.5 all conductors entering enclosures shall have abrasion protection, 334.30 nm cable shall be secured within 12" of box and every 4 1/2', 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members,210.52(A)(2) 2' wall in kitchen shall have recpt, BCC all make-up shall be done, box water heater, fans, outside nm cable
Application received  10/12/2006  
Issue permit  10/12/2006 DONE