Third Notice ELE | 2/9/2007 | 2/9/2007 | 2/13/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 12/26/2006 | 12/26/2006 | 2/9/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 10/30/2006 | 10/30/2006 | 12/26/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 10/27/2006 | 10/30/2006 | 10/30/2006 | A | PASS |
Bob Reichert
|
|
|
curtis - note: call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final
|
Final | 10/26/2006 | 10/27/2006 | 10/27/2006 | A | FAIL |
Bob Reichert
|
|
|
Curtis; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called, left corr notice,BCC all installation shall be done, panel access shall be provided, left message
|
Electrical Rough-In | 10/16/2006 | 10/17/2006 | 10/17/2006 | A | PASS |
Bob Reichert
|
|
|
curtis ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ric front and counters ok
|
Final | 10/13/2006 | 10/16/2006 | 10/16/2006 | A | FAIL |
Bob Reichert
|
|
|
curtis; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, left corr notice, nec 300.4(D) edge of mc cable shall be 1 1/4" from edge of framing members, 330.24 bend radius of mc cable shall be 7x diameter of sheath, 330.30(B) mc cable shall be strapped within 12" of box,110.12(C) there shall be no damaged cable, 210.62 showroom receptacles shall be installed every 12' or fraction thereof for show windows, BCC no violations shall be retained
|
Electrical Rough-In | 10/13/2006 | 10/13/2006 | 10/13/2006 | P | CANC |
Bob Reichert
|
|
|
###-#### curtis talked to contr, can't get in/out mall in pm, asked him to schedule am inspection
|
Application received | | | 10/13/2006 | | |
|
|
|
|
Issue & PRINT permit | | | 10/13/2006 | | DONE |
|
|
|
|