Final | 5/29/2007 | 5/29/2007 | 5/29/2007 | P | PASS |
Jack Frank
|
|
|
Garage Entry Access 0813E Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok
|
Electrical Rough-In | 10/27/2006 | 10/27/2006 | 10/27/2006 | P | PART |
Jack Frank
|
|
|
allen Note: approval to cover trench; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Rough-In Permanent Service | 10/20/2006 | 10/20/2006 | 10/20/2006 | P | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 10/20/2006 at 5:53:16 AM. Contact: ###-####. R/I OK P/S U/G N OK
|
Reinspection Fee (no hold) | 10/19/2006 | 10/19/2006 | 10/19/2006 | P | NR |
Bob Reichert
|
|
|
see notes in nr inspection
|
Rough-In Permanent Service | 10/19/2006 | 10/19/2006 | 10/19/2006 | P | NR |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/19/2006 at 10:36:02 AM. Contact: ###-####. met elect, called, left message, builder still has to build wall, elect still fixing corrections. Need to call when done.
|
Rough-In Permanent Service | 10/16/2006 | 10/17/2006 | 10/17/2006 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/16/2006 at 11:15:26 PM. Contact: ###-####. corr. called 250.104(A)(1) shall bond copper piping with #2 copper, 314.16 box fill, 210.52(A) outlet spacing missing wall in basement theater, 314.17(C) replace all 2,3,4, gang boxes broken out clamps, 300.4 nail plates and 11/4"
|
Rough-In Permanent Service | 10/13/2006 | 10/17/2006 | 10/16/2006 | A | CANC |
Bob Reichert
|
|
|
.; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Disp set to [CANC] by a contractor via Hello! on Oct 16 2006 11:17PM.
|
Application received | | | 10/13/2006 | | |
|
|
|
|
Issue permit | | | 10/13/2006 | | DONE |
|
|
|
|