Telephone call | | | 4/3/2007 | | DONE |
|
|
|
call to Debbie w/ Quality Ele, re difference btwn their fv and general's fv. She will call back.
|
Telephone call | | | 4/3/2007 | | DONE |
|
|
|
debbie w/ cloverdale called and thier fv is $35,569
|
Third Notice ELE | 3/2/2007 | 3/2/2007 | 3/7/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 2/9/2007 | 2/9/2007 | 3/2/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 1/26/2007 | 1/26/2007 | 2/9/2007 | | DONE |
Bob Reichert
|
|
|
|
Final | 1/25/2007 | 1/26/2007 | 1/26/2007 | A | PASS |
Bob Reichert
|
|
|
Requesting a final inspection. Phone #: ###-#### corr made, ok to final
|
Final | 1/24/2007 | 1/25/2007 | 1/25/2007 | A | FAIL |
Bob Reichert
|
|
|
Requesting a final inspection. Phone #: ###-#### called, left corr notice, nec 605.7 multiwire branch ckts to partitions shall simultaneously disconnect at panelboard where ckt originates, 330.30(B) mc cable shall be strapped within 12" of panel, 408.4 circuit directory shall be permanent, clear, and concise, 110.3(A) equipment shall be listed and labelled, BCC no violations shall be retained, BCC 4-05-33(A)(B) all equipment shall be listed and labelled by a nationally recognized testing laboratory
|
Final | 1/12/2007 | 1/16/2007 | 1/16/2007 | A | NR |
Bob Reichert
|
|
|
Requesting a Final inspection. Please use the West entrance. Phone #: ###-#### not done, see ri for ceilings
|
Electrical Rough-In | 1/12/2007 | 1/16/2007 | 1/16/2007 | A | PART |
Bob Reichert
|
|
|
Requesting inspection to cover ceilings. Please use the West entrance. Phone #: ###-#### 1st floor north of hall and east 1/2 only ok to cover clg, fire alarm and lv not terminated , called contr, need panel scheds, no wiring to be left on grid, find out what balance of work is and who doing, no upstairs inspections done yet, no inspections in existing parts of bldg done yet
|
Final | 1/9/2007 | 1/11/2007 | 1/11/2007 | A | FAIL |
Jack Frank
|
|
|
Requesting a Final inspection. Phone #: ###-#### no access
|
Electrical Rough-In | 1/9/2007 | 1/11/2007 | 1/11/2007 | A | FAIL |
Jack Frank
|
|
|
Requesting inspection to cover ceilings. Phone #: ###-#### no access
|
Reinspection Fee (no hold) | 1/11/2007 | 1/11/2007 | 1/11/2007 | P | DONE |
Jack Frank
|
|
|
Requesting inspection to cover ceilings. Phone #: ###-#### fee due no access
|
Conference | 12/21/2006 | 12/22/2006 | 12/22/2006 | A | DONE |
Bob Reichert
|
|
|
Requesting a consultation at the job site. ; Phone #: ###-#### Internet Inspection Request from: Dan Hardisty reviewed intent of correction notice written and what not in scope of contr work
|
Electrical Rough-In | 12/11/2006 | 12/12/2006 | 12/12/2006 | A | FAIL |
Bob Reichert
|
|
|
Requesting inspection to cover ceiling for area North of main corridor.; Phone #: ###-#### Internet Inspection Request from: Dan Hardisty called, left corr notice, BCC no violations shall be retained, NEC 725.3 abandoned Cl 2,3 PLTC cables shall be removed, 300.4(C) cables or raceway type wiring methods shall be supported according to their applicable articles
|
Electrical Rough-In | 10/13/2006 | 10/16/2006 | 10/16/2006 | P | PASS |
Bob Reichert
|
|
|
Requesting an inspection to cover.; Phone #: ###-#### Internet Inspection Request from: Dan Hardisty walls only ok to cover
|
Application received | | | 10/13/2006 | | DONE |
|
|
|
This permit was created on the web by Dan Hardisty
|