Temporary Service | 10/26/2006 | 10/26/2006 | 10/26/2006 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/26/2006 at 7:56:36 AM. Contact: ###-####. corr made, t/s o/h n ok
|
Reinspection Fee (no hold) | 10/24/2006 | 10/24/2006 | 10/24/2006 | A | FAIL |
Bob Reichert
|
|
|
see failed description
|
Temporary Service | 10/23/2006 | 10/24/2006 | 10/24/2006 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/23/2006 at 3:05:53 PM. Contact: ###-####. called, left message, left corr notice, nec 250.24(B) an unspliced main bonding kumper shall be used to connect the equipment grounding conductor and the service disconnect enclosure to the grounded conductor
|
Application received | | | 10/20/2006 | | DONE |
|
|
|
This permit was created on the web by Zane Robertson
|