Case Summary (ELE) | | | 4/13/2016 | | DONE |
|
|
|
|
Third Notice ELE | 2/9/2007 | 2/9/2007 | 2/27/2007 | | DONE |
|
|
|
This permit finaled on the web by Randy Fletcher
|
Second Notice ELE | 12/26/2006 | 12/26/2006 | 2/9/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 10/26/2006 | 10/26/2006 | 12/26/2006 | | DONE |
Jack Frank
|
|
|
|
Electrical Rough-In | 10/25/2006 | 10/25/2006 | 10/26/2006 | P | PASS |
Jack Frank
|
|
|
My cell number is ###-####, thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher
|
Final | 10/26/2006 | 10/26/2006 | 10/26/2006 | A | PASS |
Jack Frank
|
|
|
My cell number is ###-####, thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher
|
Final | 10/24/2006 | 10/25/2006 | 10/25/2006 | A | CANC |
Mike Kinnear
|
|
|
Cell phone number is ###-####, thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher Inspection cancelled from web by: Randy Fletcher
|
Final | 10/23/2006 | 10/24/2006 | 10/24/2006 | A | FAIL |
Jack Frank
|
|
|
Business opens at 9am. thanks. Randy ###-####; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher corr. called 210.8(B) gfci all 120 V recepts in counter area, 250.122 shall grd boxes and install #10 for 30 amp circuit, 110.b needs GE breakers, check box fill 4sq below panel, and derate conductors 3/4 emt
|
Final | 10/23/2006 | 10/23/2006 | 10/23/2006 | P | CANC |
Mike Kinnear
|
|
|
Any questions, my cell number is ###-####; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher Inspection cancelled from web by: Randy Fletcher
|
Owner Supplied Equipment | | | 10/23/2006 | | |
|
|
|
|
Application received | | | 10/23/2006 | | DONE |
|
|
|
This permit was created on the web by Randy Fletcher
|