Final | 2/7/2007 | 2/7/2007 | 2/7/2007 | A | PASS |
Pat Lass
|
|
|
garage codes are 3244 or 1234 Phone #: ###-####
|
Permanent Service | 12/6/2006 | 12/6/2006 | 12/6/2006 | P | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla P/S U/g N Ok
|
Permanent Service | 11/30/2006 | 11/30/2006 | 11/30/2006 | P | FAIL |
Pat Lass
|
|
|
###-#### now has half inch clearing from post; Phone #: ###-#### Internet Inspection Request from: Cevyn Recla post is still in front of the service equipment.
|
Rough-In Permanent Service | 11/20/2006 | 11/20/2006 | 11/20/2006 | P | PART |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla ok cover ri note service not ready also need access to grounding electrode connection
|
Rough-In Permanent Service | 11/20/2006 | 11/20/2006 | 11/20/2006 | A | FAIL |
Bob Reichert
|
|
|
Internet Inspection Request from: Cevyn Recla called, left corr notice, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 box shall be flush in combustible walls, 250.86 shall ground metal boxes, 334.30 se cable shall be secured within 12" of box, 300.15 all cable shall terminate in boxes, 110.26 work space shall be provided about electrical equipment (service), BCC all make-up shall be done
|
Application received | | | 10/24/2006 | | |
|
|
|
|
Issue & PRINT permit | | | 10/24/2006 | | DONE |
|
|
|
|