Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE06-03958
StatusFinaled
Name ELCOR ELECTRIC
Site Address 600 N MILWAUKEE ST
Project Name 
Customer Number29391
ePlanReview 
Description
Electrical Permit - Addition: Remodel
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice ELE12/26/200612/26/200612/29/2006 DONE
This permit finaled on the web by Ryan Christensen
First Notice12/8/200612/8/200612/26/2006 DONE
DetailsBob Reichert
Final12/8/200612/8/200612/8/2006APASS
DetailsBob Reichert
customer has job open at 9am; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to final, corrections made
Electrical Rough-In11/15/200611/15/200611/15/2006APART
DetailsJack Frank
ceiling cover rough in; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ceiling above bar area corr. posted on bdl permit for support of cables and raceways ceilings around bar area
Electrical Rough-In10/27/200610/30/200610/30/2006PPART
DetailsJack Frank
Reinspection for (1) Ceiling cover in west dining area. (2) Entry to kitchen.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen walls and ceiling in west din. area only
Electrical Rough-In10/25/200610/26/200610/26/2006AFAIL
DetailsJack Frank
(1)Ceiling cover in west dining area. (2)Entry to kitchen. ** RESTAURANT OPENS AT 11:00AM. PLEASE INSPECT BEFORE IT OPENS. Thank you!!***; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corr. called300.11(A) shall installsupport per NEC and structural, 410.67(C) all wiring to recess fixtures is branch circuit, 330.30(B), 348.30(A) secure MC and FMC within 12" of boxes and boxes at recess fixtures, 300.4*D) 11/4" for cables parallel to studs
Application received  10/25/2006 DONE
This permit was created on the web by Ryan Christensen