Second Notice ELE | 12/26/2006 | 12/26/2006 | 12/29/2006 | | DONE |
|
|
|
This permit finaled on the web by Ryan Christensen
|
First Notice | 12/8/2006 | 12/8/2006 | 12/26/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 12/8/2006 | 12/8/2006 | 12/8/2006 | A | PASS |
Bob Reichert
|
|
|
customer has job open at 9am; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to final, corrections made
|
Electrical Rough-In | 11/15/2006 | 11/15/2006 | 11/15/2006 | A | PART |
Jack Frank
|
|
|
ceiling cover rough in; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ceiling above bar area corr. posted on bdl permit for support of cables and raceways ceilings around bar area
|
Electrical Rough-In | 10/27/2006 | 10/30/2006 | 10/30/2006 | P | PART |
Jack Frank
|
|
|
Reinspection for (1) Ceiling cover in west dining area. (2) Entry to kitchen.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen walls and ceiling in west din. area only
|
Electrical Rough-In | 10/25/2006 | 10/26/2006 | 10/26/2006 | A | FAIL |
Jack Frank
|
|
|
(1)Ceiling cover in west dining area. (2)Entry to kitchen. ** RESTAURANT OPENS AT 11:00AM. PLEASE INSPECT BEFORE IT OPENS. Thank you!!***; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corr. called300.11(A) shall installsupport per NEC and structural, 410.67(C) all wiring to recess fixtures is branch circuit, 330.30(B), 348.30(A) secure MC and FMC within 12" of boxes and boxes at recess fixtures, 300.4*D) 11/4" for cables parallel to studs
|
Application received | | | 10/25/2006 | | DONE |
|
|
|
This permit was created on the web by Ryan Christensen
|