Permanent Service | 10/30/2006 | 10/30/2006 | 10/30/2006 | P | PASS |
Bob Reichert
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s o/h n ok
|
Permanent Service | 10/26/2006 | 10/27/2006 | 10/27/2006 | A | FAIL |
Bob Reichert
|
|
|
Bob Tomlinson ###-#### called contr, left corr notice, nec 110.26(A)(3) working space shall be clear from grade up to 6 1/2' over panel, IPCO requires min 2" mast for o/h service
|
Issue PAID IN FULL permit | | | 10/26/2006 | | DONE |
|
|
|
|
Application received | | | 10/25/2006 | | |
|
|
|
|