Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE06-04004
StatusExpired
Name STRICKLIN N D & D F TRUST
Site Address 6211 W YORK ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/17/20077/18/20077/18/2007PFAIL
DetailsBob Reichert
1:00 please...Duane ###-#### met owner, left correction notice, told owner he has to have contractor permit and final installation, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 314.17(C) nm cable shall be strapped within 8" of box, 312.5 all conductors entering enclosure shall have abrasion protection, 250.53(B)&(G) electrodes shall be minimum 6' apart and driven in flush with or below grade, 406.8(B) outside recpts shall have enclosure that is weatherproof whether or not plug is inserted, 300.14 shall provide minimum 6" free length conductor at each box, 110.3(B) listed equipment shall be installed per instruction included with with listing (tighten clamps), BCC must update permit for service request
Change Status to I  7/17/2007 DONE
Per Jim Schmer
Electrical Rough-In4/2/20074/3/20074/3/2007ACANC
DetailsBob Reichert
duane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, told owner permit cancelled, he was not happy, said would do as he pleased, and hung up
VOIDED CHANGE STATUS  4/3/2007 DONE
Per Jim Schmer this is not the owners primary residence so must have an electrical contractor get thier own permit///4/3/07 BAS
Conference3/20/20073/21/20073/21/2007ADONE
DetailsBob Reichert
Dwayne; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called owner, told him permit void, has to get elect contractor to do work and pull permit for any inspections, he will do. He is property owner, but does not live there, and rents out property.
Conference3/19/20073/19/20073/19/2007PNH
DetailsBob Reichert
dwayne - pls call first; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called 2x, left messages, went to site, left no access card, called 324, told him that people are renting the property and the owner built garage, 324 called and said to pull permit since this not owners principle residence
Final3/14/20073/14/20073/14/2007PFAIL
DetailsBob Reichert
duane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told people would leave corr notice, nec300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 314.17(C) nm cable shall be stapled within 8" of box, 230.24(A) service conductors shall be 8' above roof surface, 250.64(C) gec shall not be spliced, 250.52(A)(3) shall use concrete encased electrode, 312.5 all conductors entering enclosures shall have abrasion protection,240.4 conductors shall be protected against overcurrent according to their ampacity specified in 310.15, BCC all make-up shall be done and inspected prior to device installation
Application received  10/27/2006  
Issue PAID IN FULL permit  10/27/2006