Telephone call | | | 4/17/2007 | | DONE |
|
|
|
spoke w/ dj, she forgot to check fv, however she stated she would check it today and call me back today.
|
Telephone call | | | 4/17/2007 | | DONE |
|
|
|
spoke w/ dj, she confirmed fv is $3100. she said gc had mark up for their costs.
|
Second Notice ELE | 12/26/2006 | 12/26/2006 | 1/4/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 11/21/2006 | 11/21/2006 | 12/26/2006 | | DONE |
Jack Frank
|
|
|
|
Final | 11/21/2006 | 11/21/2006 | 11/21/2006 | P | PASS |
Jack Frank
|
|
|
reinspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman ok card signed
|
Final | 11/20/2006 | 11/21/2006 | 11/21/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman corr. called 110.3(B) use sq D breakers only, 406.4(D) outlets set back in steel plates, 408.4 needs panel directory noting location purpose and use
|
Electrical Rough-In | 11/1/2006 | 11/1/2006 | 11/1/2006 | P | PASS |
Mike Kinnear
|
|
|
reinspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman ok cover walls & hard lid ceiling only
|
Electrical Rough-In | 10/31/2006 | 11/1/2006 | 11/1/2006 | A | FAIL |
Jack Frank
|
|
|
corey - note: call for acess; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr. called 300.11(C) shall not support cables from other cables, 300.4 nail plates , remove MC and ENT from channel of steel studs, 330.30 (B) strap MC within 12" of boxes and fans
|
Application received | | | 10/31/2006 | | |
|
|
|
|
Issue permit | | | 10/31/2006 | | DONE |
|
|
|
|