Final | 1/15/2007 | 1/16/2007 | 1/16/2007 | A | PASS |
Bob Reichert
|
|
|
READY FOR FINAL RE-INSPECTION. THANKS Phone #: ###-#### corr made, ok to final
|
Permanent Service | 1/16/2007 | 1/16/2007 | 1/16/2007 | A | CANC |
Bob Reichert
|
|
|
READY FOR FINAL RE-INSPECTION. THANKS Phone #: ###-#### p/s o/h rec ok
|
Final | 11/7/2006 | 11/13/2006 | 11/13/2006 | A | FAIL |
Bob Reichert
|
|
|
FINAL ON SERVICE UPGRADE. ; Phone #: ###-#### Internet Inspection Request from: Barry Kendall called, left message, corr notice, nec 250.50 shall use warter pipe as gnd electrode where enters bldg, 110.26(A) work space shall be clear and safe in front of elect service, 230.24(A) service conductor over roof shall be 8', range and dryer shall be 4-wire ckts
|
Application received | | | 11/1/2006 | | DONE |
|
|
|
This permit was created on the web by Barry Kendall
|