Information based on query as of Saturday, August 17, 2024.
Permit Information
Permit NumberELE06-04144
StatusExpired
Name BLACKHAM ELECTRIC
Site Address 1816 S BROXON ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Service11/6/200611/7/200611/7/2006AFAIL
DetailsBob Reichert
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy called, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be complete, clear, concise, and specific, 110.26(A) clear work space shall be provided per code(1) depth and (3) height, 250.140 range and dryer recpts and cords shall be grounded,BCC address shall be posted and correct
Application received  11/6/2006  
Issue permit  11/6/2006 DONE