Permanent Service | 11/6/2006 | 11/7/2006 | 11/7/2006 | A | FAIL |
Bob Reichert
|
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy called, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be complete, clear, concise, and specific, 110.26(A) clear work space shall be provided per code(1) depth and (3) height, 250.140 range and dryer recpts and cords shall be grounded,BCC address shall be posted and correct
|
Application received | | | 11/6/2006 | | |
|
|
|
|
Issue permit | | | 11/6/2006 | | DONE |
|
|
|
|