Second Notice ELE | 5/29/2007 | 5/29/2007 | 5/31/2007 | | DONE |
|
|
|
This permit finaled on the web by Kathy Briggs
|
First Notice | 5/17/2007 | 5/17/2007 | 5/29/2007 | | DONE |
Jack Frank
|
|
|
|
Final | 5/17/2007 | 5/17/2007 | 5/17/2007 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok listing problem resolved
|
Final | 4/6/2007 | 4/6/2007 | 4/6/2007 | P | CANC |
Jack Frank
|
|
|
Phone #: ###-#### still needs listing or field evaluation for 4 battery racks, all they have is backwards RU generator ok ETL field tested
|
Permanent Service | 3/22/2007 | 3/23/2007 | 3/23/2007 | A | CANC |
Bob Reichert
|
|
|
Insp for temp occupancy. Phone #: ###-#### wrong type, see final
|
Final | 3/23/2007 | 3/23/2007 | 3/23/2007 | A | PART |
Bob Reichert
|
|
|
Insp for temp occupancy. Phone #: ###-#### signed t/o card, left corr notice, nec 408.4 shall complete circuit schedules, 605.7 shall use multi-pole breakers with common trip for furniture, 422.31 shall provide dishwasher disconnect, BCC shall finish panel covers, all equipment shall be listed by a nationally recognized testing laboratory (48v dc)
|
Electrical Rough-In | 3/6/2007 | 3/6/2007 | 3/6/2007 | P | PART |
Jack Frank
|
|
|
Ceiling cover inspection. Phone #: ###-#### all ceilings ok
|
Electrical Rough-In | 2/6/2007 | 2/7/2007 | 2/7/2007 | A | PART |
Jack Frank
|
|
|
Partial ceiling cover inspection. Phone #: ###-#### anop
|
Rough-In Permanent Service | 1/16/2007 | 1/16/2007 | 1/16/2007 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### p/s u/g new ok
|
Rough-In Permanent Service | 1/12/2007 | 1/16/2007 | 1/16/2007 | A | PART |
Jack Frank
|
|
|
Phone #: ###-#### conference ok only
|
Electrical Rough-In | 12/18/2006 | 12/19/2006 | 12/19/2006 | A | PART |
Jack Frank
|
|
|
Service ground inspection. ; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok also conference ok
|
Electrical Rough-In | 12/5/2006 | 12/6/2006 | 12/6/2006 | A | PART |
Jack Frank
|
|
|
Underground cover inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs u/g ok contr will secure permit for ground ring installation a outfit from canada and the excavator was installing it no cover for grd ring u/g ok only
|
Electrical Rough-In | 11/28/2006 | 11/29/2006 | 11/29/2006 | A | PART |
Jack Frank
|
|
|
Wall cover inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs walls anop
|
Electrical Rough-In | 11/17/2006 | 11/20/2006 | 11/20/2006 | P | PART |
Jack Frank
|
|
|
Wall cover inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs walls anop
|
Application received | | | 11/9/2006 | | DONE |
|
|
|
This permit was created on the web by Kathy Briggs
|