ELE-Aging Inspection | 11/27/2007 | 11/27/2007 | 11/27/2007 | | DONE |
Jack Frank
|
|
|
|
DOC - Permit Expired | 11/27/2007 | 11/27/2007 | 11/27/2007 | A | PASS |
Jack Frank
|
|
|
mobile kitchen removed from site
|
Permanent Service | 11/20/2006 | 11/21/2006 | 11/21/2006 | A | FAIL |
Jack Frank
|
|
|
bill Note: please call for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr met contr. BCC & NEC mobile kitchen requires Idaho state tag yours only has Oregon, also no violations retained correct all wiring altered from manufactures wiring
|
Permanent Service | 11/14/2006 | 11/14/2006 | 11/15/2006 | P | FAIL |
Jack Frank
|
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called told contr he needs to check out kitchen shack wiring, and wire it then call for r/i inspection permit was for a R V comm. kit. shack
|
Final | 11/13/2006 | 11/14/2006 | 11/14/2006 | A | FAIL |
Jack Frank
|
|
|
william ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr. called no final p/s 250.64(E) shall use kisted fiiting for GEC, 250.56 needs 2 grd rods, 250.24(A)(1) shall make connection between grd and neutral
|
Application received | | | 11/13/2006 | | |
|
|
|
|
Issue permit | | | 11/13/2006 | | DONE |
|
|
|
|