Permanent Service | 11/16/2006 | 11/17/2006 | 11/17/2006 | A | PASS |
Bob Reichert
|
|
|
randall ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told owner to triangulate guy wires, p/s o/h rec ok
|
Permanent Service | 11/15/2006 | 11/16/2006 | 11/16/2006 | A | FAIL |
Bob Reichert
|
|
|
###-#### randall--service is outside talked to owner, said to call when done, nec 250.52(A) shall ground water pipe coming in, 250.52(A)(5) rod electrodes shall be 8" long,250.53(B) rod electrodes shall be 6" apart, 200.6 shall id grounded conductor, 408.4 shall complete panel schedule
|
Application received | | | 11/15/2006 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 11/15/2006 | | DONE |
|
|
|
|