Final | 12/27/2006 | 12/27/2006 | 12/27/2006 | P | PASS |
Jack Frank
|
|
|
dave ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
|
Electrical Rough-In | 12/18/2006 | 12/19/2006 | 12/19/2006 | A | PASS |
Jack Frank
|
|
|
Dave; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett r/i ok
|
Electrical Rough-In | 12/18/2006 | 12/18/2006 | 12/18/2006 | P | NR |
Pat Lass
|
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Patricia Smith will reschedual when ready and have person on site to open things up
|
Electrical Rough-In | 11/24/2006 | 11/24/2006 | 11/24/2006 | P | FAIL |
Jack Frank
|
|
|
DAVE; Phone #: ###-#### NoTE : PATIO COVER OUT BACK Internet Inspection Request from: Cathy Chiles corr. called 314.17(A B C )shall use fittings where cables enter wiremold per manufactures instructions (386.6) also 2 gang cut in boxes with clamps broken out shall be replaced, 386.22 and 110.3(B) manufactures instructions is MNB cable allowed in wiremold all wiremold and sun room manufactures instructions shall be at job site, and 300.10 & 12 electrical and mechanical continuity shall be provides all all wiring methods used
|
Application received | | | 11/16/2006 | | |
|
|
|
|
Issue permit | | | 11/16/2006 | | DONE |
|
|
|
|