Second Notice ELE | 12/26/2006 | 12/26/2006 | 12/26/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
Second Notice ELE | 12/26/2006 | 12/26/2006 | 12/26/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 11/22/2006 | 11/22/2006 | 12/26/2006 | | DONE |
Bob Reichert
|
|
|
|
First Notice | 11/22/2006 | 11/22/2006 | 12/26/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 11/22/2006 | 11/22/2006 | 11/22/2006 | P | PASS |
Bob Reichert
|
|
|
questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer t/s ok to final, see t/s
|
Temporary Service | 11/22/2006 | 11/22/2006 | 11/22/2006 | P | PASS |
Bob Reichert
|
|
|
questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer corr made, t/s o/h n ok
|
Reinspection Fee (no hold) | 11/22/2006 | 11/22/2006 | 11/22/2006 | P | FAIL |
Bob Reichert
|
|
|
see fail
|
Final | 11/21/2006 | 11/22/2006 | 11/22/2006 | A | FAIL |
Bob Reichert
|
|
|
temp power insp. questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer called, left corr notice, nec 230.74 service disc shall disconnect all ungrounded conductors simultaneously,312.5 shall provide abrasion protection for all conductors entering enclosure, 250.53(G) electrode shall be flush with or below ground, 408.4 circuit directory shall be correct, BCC job id sticker shall be posted
|
Application received | | | 11/21/2006 | | DONE |
|
|
|
This permit was created on the web by Heather Packer
|