Telephone call | | | 7/10/2007 | | DONE |
|
|
|
tlk to mainline ele ###-#### to verify the difference from theirs to contractors - will contact me back this week 11:40 am
|
Third Notice ELE | 4/25/2007 | 4/25/2007 | 4/25/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 4/9/2007 | 4/9/2007 | 4/25/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 3/26/2007 | 3/26/2007 | 4/18/2007 | | DONE |
Jack Frank
|
|
|
|
Final | 3/26/2007 | 3/26/2007 | 3/26/2007 | P | PASS |
Jack Frank
|
|
|
cindy - on site in another building; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok no card
|
Final | 3/23/2007 | 3/26/2007 | 3/26/2007 | A | NH |
Jack Frank
|
|
|
Robert; Phone #: ###-#### Internet Inspection Request from: Stacie Backus notice posted called no response
|
Final | 3/23/2007 | 3/23/2007 | 3/23/2007 | P | FAIL |
Jack Frank
|
|
|
Robert; Phone #: ###-#### Internet Inspection Request from: Stacie Backus corr. fee due 300.10&12 maintain elect,& mech continuity for mc at high bay fixtures, ID white wire mc in subpanel 20 amp 2pole breaker
|
Reinspection Fee (no hold) | 3/23/2007 | 3/23/2007 | 3/23/2007 | P | DONE |
Jack Frank
|
|
|
Robert; Phone #: ###-#### Internet Inspection Request from: Stacie fee due more violations created corr posted
|
Final | 3/21/2007 | 3/21/2007 | 3/21/2007 | P | FAIL |
Jack Frank
|
|
|
robert - ceiling and final; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr. called 410.30(C)(1) fixture shall be located directly below the outlet, 600.5(A) shall install required sign branch circuit see added r/i
|
Electrical Rough-In | 3/21/2007 | 3/21/2007 | 3/21/2007 | P | CANC |
Jack Frank
|
|
|
robert - ceiling and final; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ceiling ok
|
Permanent Service | 2/20/2007 | 2/20/2007 | 2/20/2007 | P | PASS |
Jack Frank
|
|
|
robert ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s u/g new ok
|
Electrical Rough-In | 1/4/2007 | 1/5/2007 | 1/5/2007 | A | PASS |
William E Thomas
|
|
|
robert ; Phone #: ###-#### Internet Inspection Request from: Patricia Smit 1. walls only-ri ok
|
Electrical Rough-In | 1/3/2007 | 1/3/2007 | 1/3/2007 | P | FAIL |
Jack Frank
|
|
|
robert Note: walls and perman panel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr fee due called 300.4 nail plates , 250.24(A)(5) isolate grds and neutrals at subpanel 408.41 only 1 neutral wire per terminal
|
Reinspection Fee (no hold) | 1/3/2007 | 1/3/2007 | 1/3/2007 | P | DONE |
Jack Frank
|
|
|
robert Note: walls and perman panel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles fee dueall corrections not made new ones created
|
Electrical Rough-In | 12/22/2006 | 12/26/2006 | 12/26/2006 | A | FAIL |
Bob Reichert
|
|
|
robert-- ###-#### called left corr notice nec 200.6(A) grounded conductor 6 awg or smaller shall be identified by white or gray or 3 continuous white stripes along entire length, 250.119(A) insulated ground shall be green or have green with yellow stripes for id, 300.4(A)&(D) edge of holes and cable shall be 1 1/4" from edge of framing member
|
Application received | | | 12/22/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 12/22/2006 | | |
|
|
|
|
Issue & PRINT permit | | | 12/22/2006 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 12/22/2006 | | |
|
|
|
|