Final | 3/13/2007 | 3/13/2007 | 3/13/2007 | P | PASS |
Bob Reichert
|
|
|
Candy pls call prior for lock box code other number (###-####); Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok to final
|
Final | 3/12/2007 | 3/12/2007 | 3/12/2007 | P | NH |
Bob Reichert
|
|
|
candy or sharon - pls call for secaurity code; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called for code, no lock box, need to call when available
|
Electrical Rough-In | 1/11/2007 | 1/12/2007 | 1/12/2007 | A | PASS |
Bob Reichert
|
|
|
jake; Phone #: ###-####, or ramey ###-####, or jerry ###-#### Internet Inspection Request from: Victoria Beall corr made, ric ok
|
Electrical Rough-In | 1/10/2007 | 1/11/2007 | 1/11/2007 | A | FAIL |
Bob Reichert
|
|
|
jake - note cell# for lock box code ###-#### or ###-####; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called contr, left corr notice, nec 300.4(A) edge of bored holes shall be 1 1/4" from face of framing members, 210.52(A)(1) no wall space shall be over 6' from recpt, 334.30 nm cable shall be strapped within 12" of box, 240.24(B) each occupant shall have access to all overcurrent devices for that occupancy
|
Electrical Rough-In | 1/3/2007 | 1/3/2007 | 1/3/2007 | P | NR |
Bob Reichert
|
|
|
jake ###-#### call for lock box # called contr, said nr, left corr notice, nec violations numerous, with sheet rock down, shall wire to code, BCC no violations shall be retained
|
Electrical Rough-In | 1/2/2007 | 1/3/2007 | 1/3/2007 | A | NH |
Mike Kinnear
|
|
|
jake ; Phone #: ###-#### call for access - Internet Inspection Request from: Patricia Smith called left message reinspection fee
|
Reinspection Fee (no hold) | 1/3/2007 | 1/3/2007 | 1/3/2007 | A | NH |
Mike Kinnear
|
|
|
jake ; Phone #: ###-#### call for access - Internet Inspection Request from: Patricia Smith no access called left message
|
Application received | | | 1/2/2007 | | |
|
|
|
|
Issue permit | | | 1/2/2007 | | DONE |
|
|
|
|