Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE07-00076
StatusFinaled
Name BLACKHAM ELECTRIC
Site Address 17 S ROGER ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/4/20074/5/20074/5/2007APASS
DetailsBob Reichert
the key is under the can on the meter main Phone #: ###-#### corr made, ok to final
Final3/30/20074/2/20074/2/2007AFAIL
DetailsBob Reichert
Brandon; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, nec 210.52(E) shall install recpt at rear of dwelling, 210.70(A)(3) shall install lighting for jetted tub access and verify access hole per mfgr's instructions, 410.8(D) flourescent fixt in closet shall be min 6'' from shelf, 406.5 recpt faceplates shall seat against mounting surface, NOTE: shall provide cover for gec on dwelling and finish nailplates in garage
Electrical Rough-In1/16/20071/16/20071/16/2007PPASS
DetailsBob Reichert
underground//Brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles u/g ok to cover house to garage only
Electrical Rough-In1/10/20071/11/20071/11/2007APASS
DetailsPat Lass
brandon; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
Permanent Service1/11/20071/11/20071/11/2007PPASS
DetailsPat Lass
brandon; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
P/S U/G N Ok
Rough-In Permanent Service1/10/20071/10/20071/10/2007PFAIL
DetailsBob Reichert
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left corr notice, nec 300.4(A)&(B) edge of holes and nm cable shall be 1 1/4" from edge of framing member,314.17(C) nm cable shall be stapled within 8" of box, 210.52(A) recpt shall be placed in entry, 410.8 closet light shall be 12" from shelf, 210.52(E) recpt shall be installed at back,210.63 recpt shall be within 25' of a/c, BCC all make-up shall be done(kitchen), shall see u/g to garage
Rough-In Permanent Service1/8/20071/9/20071/9/2007ACANC
DetailsBob Reichert
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wrong type request, see ri
Electrical Rough-In1/9/20071/9/20071/9/2007APART
DetailsBob Reichert
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles back outside wall and upstairs floors ok to cover
Application received  1/8/2007  
Issue permit  1/8/2007 DONE