Final | 5/30/2007 | 5/30/2007 | 5/30/2007 | P | PASS |
Bob Reichert
|
|
|
Reinspection Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corrections made, ok to final
|
Final | 5/29/2007 | 5/29/2007 | 5/29/2007 | P | FAIL |
Bob Reichert
|
|
|
Reinspection Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called, left message, corrections not made
|
Reinspection Fee (no hold) | 5/29/2007 | 5/29/2007 | 5/29/2007 | P | FAIL |
Bob Reichert
|
|
|
Reinspection Phone #: ###-#### Internet Inspection Request from: Ryan Christensen see fail final
|
Final | 5/24/2007 | 5/24/2007 | 5/24/2007 | P | CANC |
Bob Reichert
|
|
|
Reinspection Phone #: ###-#### Internet Inspection Request from: Ryan Christensen Inspection cancelled from web by: Ryan Christensen
|
Final | 5/23/2007 | 5/24/2007 | 5/24/2007 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called left corr notice, nec 210.52(B)(1) dishwasher shall not be on small appliance branch ckt, 352.30(A) rnc shall be strapped within 3' of termination, 410.4(D) luminaire shall be listed for wet or damp location within 3' of shower space, 422.31(B) shall provide lock-out for dishwasher, BCC all boxes shall be closed and covers installed, address shall be posted
|
Rough-In Permanent Service | 1/19/2007 | 1/22/2007 | 1/22/2007 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### met contr, told to change to 13 rooms plus service, ric ok, p/s u/g n ok
|
Application received | | | 1/19/2007 | | DONE |
|
|
|
This permit was created on the web by Ryan Christensen
|