Final | 5/30/2007 | 5/30/2007 | 5/30/2007 | P | PASS |
Bob Reichert
|
|
|
Reinspection Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corrections made, ok to final
|
Final | 5/29/2007 | 5/29/2007 | 5/29/2007 | P | FAIL |
Bob Reichert
|
|
|
Reinspection Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called, corrections not made,
|
Reinspection Fee (no hold) | 5/29/2007 | 5/29/2007 | 5/29/2007 | P | FAIL |
Bob Reichert
|
|
|
Reinspection Phone #: ###-#### Internet Inspection Request from: Ryan Christensen see failed final
|
Final | 5/24/2007 | 5/24/2007 | 5/24/2007 | P | CANC |
Bob Reichert
|
|
|
Reinspection Phone #: ###-#### Internet Inspection Request from: Ryan Christensen Inspection cancelled from web by: Ryan Christensen
|
Final | 5/23/2007 | 5/24/2007 | 5/24/2007 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called, left corr notice, nec 352.30(A) rnc shall be strapped within 3' of termination, 422.31(B) shall provide dishwasher lock-out, 210.52(B)(1) dishwasher shall not be on small appliance branch ckt, BCC all switch plates shall be installed, mount button switch, provide globe guard kitchen closet, address shall be posted
|
Rough-In Permanent Service | 1/19/2007 | 1/22/2007 | 1/22/2007 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### met contr, told to change permit to 13 rooms, plus service, ric ok, p/s u/g n ok
|
Application received | | | 1/19/2007 | | DONE |
|
|
|
This permit was created on the web by Ryan Christensen
|