Final | 4/24/2007 | 4/24/2007 | 4/24/2007 | P | PASS |
Bob Reichert
|
|
|
Neil ; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
|
Rough-In Permanent Service | 2/8/2007 | 2/9/2007 | 2/9/2007 | A | PASS |
Pat Lass
|
|
|
neil; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corrections required by bob and jack have been made. R/I Ok P/S O/H R Ok
|
Permanent Service | 2/6/2007 | 2/6/2007 | 2/6/2007 | P | FAIL |
Jack Frank
|
|
|
neil; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections not made still needs 11/4" all locations, 250.52(A)(1) GRC to u/g pipe within 5ft, outlet spacing fixed panel of slider din rm called
|
Electrical Rough-In | 1/30/2007 | 1/30/2007 | 1/30/2007 | P | FAIL |
Bob Reichert
|
|
|
NEIL; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left corr notice, nec 338.10 & 334 se cable shall be secured within 12" of box, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.52(E) shall provide front outdoor recpt, 210.53(D)(2) water pipe ground shall be supplemented by additional electrode per 250.52(A)(2) thru (A)(7), BCC all make-up shall be done-switch ring in north bedroom
|
Application received | | | 1/30/2007 | | |
|
|
|
|
Issue permit | | | 1/30/2007 | | DONE |
|
|
|
|