Permanent Service | 3/28/2007 | 4/2/2007 | 4/2/2007 | P | PASS |
Jack Frank
|
|
|
Jack, #4 GEC installed to water main, Hot h20 heater bonded around all fittings.Done! thanks Loren Phone #: ###-#### see added final
|
Final | 4/2/2007 | 4/2/2007 | 4/2/2007 | P | PASS |
Jack Frank
|
|
|
Jack, #4 GEC installed to water main, Hot h20 heater bonded around all fittings.Done! thanks Loren Phone #: ###-#### ok
|
Final | 2/19/2007 | 2/20/2007 | 2/20/2007 | A | FAIL |
Jack Frank
|
|
|
service change complete! Loren Ramsey thanks Phone #: ###-#### corr called 250.52 (A)(1) & 250.66 needs #4 copper to u/g water, bond hot and cold and around insulating fitttings
|
Permanent Service | 2/20/2007 | 2/20/2007 | 2/20/2007 | A | PASS |
Jack Frank
|
|
|
p/s u/g rec. ok
|
Application received | | | 2/1/2007 | | DONE |
|
|
|
This permit was created on the web by Loren Ramsey
|