Third Notice ELE | 5/14/2007 | 5/14/2007 | 5/31/2007 | | DONE |
|
|
|
This permit finaled on the web by Kathy Briggs
|
Second Notice ELE | 4/24/2007 | 4/24/2007 | 5/14/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 4/13/2007 | 4/13/2007 | 4/24/2007 | | DONE |
Bob Reichert
|
|
|
|
Final | 4/12/2007 | 4/13/2007 | 4/13/2007 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### called, left message, left survey, nec 350.30(A) lfmc shall be securely fastened in place by an approved means within 12" of each termination point
|
Permanent Service | 2/21/2007 | 2/21/2007 | 2/21/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### p/s u/g n ok
|
Permanent Service | 2/16/2007 | 2/16/2007 | 2/16/2007 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### called, left corr notice, BCC 4-05-33 (A)(B) equipment shall be listed and labelled by a nationally recognized testing laboratory, NEC 110.3(A)(1) suitability of equipment shall be evidenced by listing or labelling, 110 12(A) unused openings shall be closed, 200.9 terminal to which grounded conductor connected shall be identified white
|
Application received | | | 2/7/2007 | | DONE |
|
|
|
This permit was created on the web by Kathy Briggs
|