Permit Information
Permit NumberELE07-00467
StatusFinaled
Name DUNHAM ELECTRIC INC
Site Address 2036 N COLE RD
Project Name 
Customer Number 
ePlanReview 
Description
Remodel and upgrade service per initial cert of value $8,000///2/9/07 BAS ///final value is $14,506 per faxed document 1-15-08ps
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice ELE12/26/200712/26/20071/15/2008 DONE
DetailsPatricia Smith
Second Notice has not been responded to.
Second Notice ELE12/4/200712/4/200712/26/2007 DONE
First Notice has not been responded to.
First Notice11/23/200711/23/200712/4/2007 DONE
DetailsMike Kinnear
Final11/21/200711/23/200711/23/2007PPASS
DetailsMike Kinnear
Phone #: ###-#### Internet Inspection Request from: Curtis Dunham corrections made ok final note signed card
Final11/20/200711/21/200711/21/2007PFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Curtis Dunham called , left correction notice, nec 408.4 circuit directory shall be clear, concise, and explanatory for each circuit, 110.3 (B) listed equipment shall be installed and operate per instructions- gfci for strip outlets
Permanent Service10/25/200710/29/200710/26/2007ACANC
DetailsBob Reichert
This is a doctor''s office, work is being done over the weekend, and we are requesting for the inspection to be first thing Monday morning so the power can be turned back on without interfering with their business. Thank you. Phone #: ###-#### Internet Inspection Request from: Curtis Dunham Inspection cancelled from web by: Curtis Dunham
Permanent Service10/18/200710/22/200710/22/2007ACANC
DetailsJack Frank
we need to have this inspected first thing in the morning if possible. We are doing the service on Saturday so we can get the doctors office back on line Monday AM. Thanks for your help. Curtis Dunham Phone #: ###-#### Internet Inspection Request from: Curtis Dunham called
Electrical Rough-In8/14/20078/14/20078/14/2007PPART
DetailsWilliam E Thomas
Curtis; Phone #: ###-#### Internet Inspection Request from: Hattie James
1. waiting rook area ok plus hard lid.
Electrical Rough-In7/30/20077/31/20077/31/2007APART
DetailsBob Reichert
curtis - some can lights have for the waiting room are on special order so we need a partial for the rest of the walls and ceiling so the job can continue forward ; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called contr, for 1 1/4" on smurf and mc, walls and ceilings except 6 can lites in waiting area ok to cover
Electrical Rough-In7/27/20077/30/20077/30/2007PCANC
DetailsBob Reichert
some can lights have for the waiting room are on special order so we need a partial for the rest of the walls and ceiling so the job can continue forward Phone #: ###-#### Internet Inspection Request from: Curtis Dunham
Final4/22/20074/23/20074/23/2007PPART
DetailsBob Reichert
Phase one south side Phone #: ###-#### Internet Inspection Request from: Curtis Dunham south 1/2 ok for t/o, signed t/o card
Electrical Rough-In2/15/20072/15/20072/15/2007APART
DetailsBob Reichert
Phone #: ###-#### corr made, ok to cover south part
Electrical Rough-In2/13/20072/13/20072/14/2007PFAIL
DetailsBob Reichert
curtis - after 2:00 please ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith thought ok, but not. Called contr, left message, nec 517.13(A) and (B) metal sheath assembly shall itself qualify as an equipment grounding return path in accordance with 250-118, equipment grounding conductor shall be part of branch circuit of listed cable
Electrical Rough-In2/9/20072/12/20072/12/2007ANR
DetailsBob Reichert
curtis ###-#### wiring shall be per nec 517.13, contr shall re-do branch circuits to exam rooms
Application received  2/9/2007  
Issue & PRINT permit  2/9/2007 DONE