Third Notice ELE | 12/26/2007 | 12/26/2007 | 1/15/2008 | | DONE |
Patricia Smith
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 12/4/2007 | 12/4/2007 | 12/26/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 11/23/2007 | 11/23/2007 | 12/4/2007 | | DONE |
Mike Kinnear
|
|
|
|
Final | 11/21/2007 | 11/23/2007 | 11/23/2007 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Curtis Dunham corrections made ok final note signed card
|
Final | 11/20/2007 | 11/21/2007 | 11/21/2007 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Curtis Dunham called , left correction notice, nec 408.4 circuit directory shall be clear, concise, and explanatory for each circuit, 110.3 (B) listed equipment shall be installed and operate per instructions- gfci for strip outlets
|
Permanent Service | 10/25/2007 | 10/29/2007 | 10/26/2007 | A | CANC |
Bob Reichert
|
|
|
This is a doctor''s office, work is being done over the weekend, and we are requesting for the inspection to be first thing Monday morning so the power can be turned back on without interfering with their business. Thank you. Phone #: ###-#### Internet Inspection Request from: Curtis Dunham Inspection cancelled from web by: Curtis Dunham
|
Permanent Service | 10/18/2007 | 10/22/2007 | 10/22/2007 | A | CANC |
Jack Frank
|
|
|
we need to have this inspected first thing in the morning if possible. We are doing the service on Saturday so we can get the doctors office back on line Monday AM. Thanks for your help. Curtis Dunham Phone #: ###-#### Internet Inspection Request from: Curtis Dunham called
|
Electrical Rough-In | 8/14/2007 | 8/14/2007 | 8/14/2007 | P | PART |
William E Thomas
|
|
|
Curtis; Phone #: ###-#### Internet Inspection Request from: Hattie James 1. waiting rook area ok plus hard lid.
|
Electrical Rough-In | 7/30/2007 | 7/31/2007 | 7/31/2007 | A | PART |
Bob Reichert
|
|
|
curtis - some can lights have for the waiting room are on special order so we need a partial for the rest of the walls and ceiling so the job can continue forward ; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called contr, for 1 1/4" on smurf and mc, walls and ceilings except 6 can lites in waiting area ok to cover
|
Electrical Rough-In | 7/27/2007 | 7/30/2007 | 7/30/2007 | P | CANC |
Bob Reichert
|
|
|
some can lights have for the waiting room are on special order so we need a partial for the rest of the walls and ceiling so the job can continue forward Phone #: ###-#### Internet Inspection Request from: Curtis Dunham
|
Final | 4/22/2007 | 4/23/2007 | 4/23/2007 | P | PART |
Bob Reichert
|
|
|
Phase one south side Phone #: ###-#### Internet Inspection Request from: Curtis Dunham south 1/2 ok for t/o, signed t/o card
|
Electrical Rough-In | 2/15/2007 | 2/15/2007 | 2/15/2007 | A | PART |
Bob Reichert
|
|
|
Phone #: ###-#### corr made, ok to cover south part
|
Electrical Rough-In | 2/13/2007 | 2/13/2007 | 2/14/2007 | P | FAIL |
Bob Reichert
|
|
|
curtis - after 2:00 please ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith thought ok, but not. Called contr, left message, nec 517.13(A) and (B) metal sheath assembly shall itself qualify as an equipment grounding return path in accordance with 250-118, equipment grounding conductor shall be part of branch circuit of listed cable
|
Electrical Rough-In | 2/9/2007 | 2/12/2007 | 2/12/2007 | A | NR |
Bob Reichert
|
|
|
curtis ###-#### wiring shall be per nec 517.13, contr shall re-do branch circuits to exam rooms
|
Application received | | | 2/9/2007 | | |
|
|
|
|
Issue & PRINT permit | | | 2/9/2007 | | DONE |
|
|
|
|