Final | 7/12/2007 | 7/12/2007 | 7/12/2007 | P | PASS |
William E Thomas
|
|
|
william; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang final ok
|
Electrical Rough-In | 6/6/2007 | 6/6/2007 | 6/6/2007 | P | PASS |
Jack Frank
|
|
|
u/g from house to garage ok
|
Electrical Rough-In | 3/2/2007 | 3/2/2007 | 3/2/2007 | P | PASS |
Bob Reichert
|
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to cover except at panel, need to see feeder coming in from house, which will be done by contr ltr
|
Electrical Rough-In | 2/28/2007 | 3/2/2007 | 3/2/2007 | A | FAIL |
Bob Reichert
|
|
|
Bill; Phone #: ###-#### Internet Inspection Request from: Stacie Backus met owner, left corr notice, nec 250.86 all metal boxes shall be grounded with approved green ground screws,334.30 nm cable shall be secured within 12" of box, 110.3(B) romex 2 screw connector shall not be used on gec, 250.148(B) grounds shall be such that continuity is not broken by device removal (tie all together in box)
|
Conference | 2/15/2007 | 2/16/2007 | 2/16/2007 | A | DONE |
Bob Reichert
|
|
|
william-- call 1st before insp -###-#### reviewed service and wiring requirements for shop
|
Application received | | | 2/15/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 2/15/2007 | | |
|
|
|
|