Final | 5/8/2007 | 5/8/2007 | 5/8/2007 | P | PASS |
Bob Reichert
|
|
|
robert ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
Permanent Service | 5/8/2007 | 5/8/2007 | 5/8/2007 | P | PASS |
Bob Reichert
|
|
|
robert ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corrections made, p/s o/h n ok
|
Rough-In Permanent Service | 5/4/2007 | 5/7/2007 | 5/7/2007 | A | FAIL |
Pat Lass
|
|
|
RC ###-#### splice in GEC, electrode not flush, plastic romex connector on GEC, 250.148, isolate neutral in sub panel, and install 2 in. imc for mast
|
(F) Reprint permit | | | 4/24/2007 | | DONE |
|
|
|
|
Conference | 3/12/2007 | 3/12/2007 | 3/12/2007 | P | DONE |
William E Thomas
|
|
|
RC Johnson ###-####//conf for electrical in shop in the back of house talked about location of the new service
|
Issue permit | | | 3/12/2007 | | DONE |
|
|
|
|
Application received | | | 2/21/2007 | | |
|
|
|
|