Final | 6/7/2007 | 6/7/2007 | 6/7/2007 | P | PASS |
William E Thomas
|
|
|
Call the electrical contractor, Dave Weil if this doesn''t pass for some reason, Thanks Mike! Phone #: ###-#### Internet Inspection Request from: KATHY WEIL final ok
|
Rough-In Permanent Service | 4/9/2007 | 4/11/2007 | 4/11/2007 | A | PASS |
Bob Reichert
|
|
|
Let Luke know if this doesn''t pass please! Phone #: ###-#### corrections made, ric ok, p/s u/g n ok
|
Electrical Rough-In | 4/9/2007 | 4/10/2007 | 4/10/2007 | P | PASS |
Bob Reichert
|
|
|
Concrete incasement inspection, thank you! Phone #: ###-#### ok to backfill gec
|
Electrical Rough-In | 4/9/2007 | 4/10/2007 | 4/10/2007 | A | PASS |
Bob Reichert
|
|
|
Ufer inspection, thank you! Phone #: ###-#### ok to pour gec only
|
Electrical Rough-In | 4/8/2007 | 4/9/2007 | 4/9/2007 | A | PASS |
Bob Reichert
|
|
|
This inspection is actually for the conduit from the house to the garage so they can get it backfilled. Phone #: ###-#### Internet Inspection Request from: KATHY WEIL Phone #: ###-#### u/g only ok to cover
|
Rough-In Permanent Service | 4/5/2007 | 4/5/2007 | 4/5/2007 | P | FAIL |
Bob Reichert
|
|
|
If you are in the Rose Hill area before noon rowhouses are ready. I just didn''t get on the inspection request time before 7:30 to request them. Thanks Mike! Phone #: ###-#### met contr, left corr notice, nec 250.52(A)(3)&BCC new construction shall have concrete encased electrode, 314.20 in walls of combustible material, boxes shall be flush with finished surface, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, BCC all u/g shall be inspected before cover, approved plans shall be on job, address shall be posted
|
Application received | | | 2/21/2007 | | |
|
|
|
|
Issue & PRINT permit | | | 2/21/2007 | | DONE |
|
|
|
|