Final | 4/6/2007 | 4/6/2007 | 4/6/2007 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 4/6/2007 at 9:52:20 AM. Contact: ###-####. ok final
|
Electrical Rough-In | 2/26/2007 | 2/26/2007 | 2/26/2007 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 2/26/2007 at 9:44:52 AM. Contact: ###-####. ok
|
Electrical Rough-In | 2/24/2007 | 2/26/2007 | 2/26/2007 | A | NH |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 2/24/2007 at 8:33:46 AM. Contact: ###-####. not home, no answer with contractors phone
|
Electrical Rough-In | 2/22/2007 | 2/23/2007 | 2/23/2007 | P | FAIL |
Bob Reichert
|
|
|
Please call John Phone #: ###-#### called contr, left corr notice, 300.4(A) & (D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 250.86 metal boxes shall be grounded, 314.17(C) nm cable shall be srecured within 8" of box, BCC no violations shall be retained- splices shall be accessible and in box
|
Application received | | | 2/22/2007 | | DONE |
|
|
|
This permit was created on the web by John Campbell
|