Second Notice ELE | 6/21/2007 | 6/21/2007 | 6/26/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 5/29/2007 | 5/29/2007 | 6/21/2007 | | DONE |
Bob Reichert
|
|
|
|
Final | 5/29/2007 | 5/29/2007 | 5/29/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 5/29/2007 at 8:20:54 AM. Contact: ###-####. n ok to final
|
Electrical Rough-In | 2/28/2007 | 3/1/2007 | 3/1/2007 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 2/28/2007 at 7:37:32 PM. Contact: ###-####.
|
Electrical Rough-In | 2/27/2007 | 2/27/2007 | 2/27/2007 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/27/2007 at 10:03:43 AM. Contact: ###-####. called , left message, left corr notice, nec 300.4(A)&(D) edge of bored holes, mc cable, and ent shall be 1 1/4" from edge of framing member, BCC no violations shall be retained
|
Application received | | | 2/27/2007 | | |
|
|
|
|
Issue permit | | | 2/27/2007 | | DONE |
|
|
|
|